chinese english
News
Location:Home << News <<
Author: Date:2014-10-10 Back

 

1, the electronic fence system security device wiring design should be consistent with current national standard "design specification for industrial enterprise communication" in the national implementation of the requirements and the existing relevant provisions and norms.
 
2, the front end host detector and burglary line generally should all adopt copper core shielding wire.
 
3, the signal transmission line pressure shall not be lower than the AC 250V, core cross-sectional area shall meet the requirements of system technology, should also meet the needs of the mechanical strength, the minimum cross-section wire shall not be less than the following values:
Class line minimum core section (square mm)
 
Wear pipe laying insulation wire 1
 
Line groove laying insulation wire 0.75
 
Multi core cable 0.50
 
4, the detector power supply transmission line, should use copper core pressure not less than the exchange of 500V insulated strands of wire or cable, power supply distance above 50M power line distance, the wire diameter not less than phi 0.75mm.
 
5, the path selection should be based on appearance, construction convenient maintenance as the principle, take the line path should be short, safe and reliable.
 
6, as far as possible hidden, to prevent the destruction of.
 
7, strong, weak in general should be laid separately, in case the line is broken, the host signal transmitting device is electric pulse damage, resulting in unnecessary loss of property.
 
8, to ensure that the pulse signal transmission line enclosure host integrity.
Network electronic fence
Wireless electronic fence
Perimeter protection
Shenzhen BTD Tech. Co. LTD
Add:5th Floor, 51 Industrial Park, Liguang District, New Yongfeng, Liguang Village, Yangtaishan Road, Guantian Community, Shiyan Street, Baoan District, Shenzhen Design:WeB design 粤ICP备10227210号
Tel:0755-23042858 Fax:0755-29004983 Email:cashier001@sz-btd.com